DATA CENTER POWER SOLUTIONS <<<<< UPS POWER ACCESORIES <<<<< DATA CENTER POWER SOLUTIONS


Harmonic currents generated by nonlinear loads can cause problems in the power system and more particularly in Conventional Transformers designed for Linear loads due to overheating resulting in premature failure.

Any Computer Installation with large number of Computers and peripherals generate / demand large value of Harmonic currents basically for the simple reason that they all have SMPS power supplies at the input with large nonlinear demands and crest factors in the range of 5-7.This results in very large harmonic current demand.Harmonics generate additional heat in the transformers at the input and result in excessive overheating and burning of normal rated transformers.


Merely de-rating Conventional transformers does not solve the problem.

Harmonic currents are currents which have frequencies that are multiples of the fundamental (power supply) frequency i.e. 50Hz. The harmonic currents superimposed on the fundamental current result in the non-sinusoidal current waveforms associated with nonlinear loads.

 




WHAT IS K FACTOR AND K-RATING?


K factor is property of any load system which is either fully linear or fully non linear harmonic load system or is a combination of the two. The K-Factor number varies with different combinations as given by table below.

Underwriters laboratory (UL) has devised a rating system to indicate the capabili`ty of a transformer to handle harmonic loads. The ratings are described in UL1561 and are known as transformer K-13. K-Factor is a weighting of the harmonic load currents according to their effects on transformer heating, as derived from ANSI/IEEE C57.110. A K-Factor of 1.0 indicates a linear load (no harmonics). The higher the K-Factor, the greater the harmonic heating effects:  K-Factor = (Ih)²h²   where Ih is the load current at harmonic h, expressed in a per-unit basis such that the total RMS current equals one. This means that the higher the harmonic number its contribution to K-factor is more as

in the formulae it is squared.













 

       




​        

        K RATED TRANSFORMERS-DESIGN FACTORS         


AND CONSTRUCTIONAL FEATURES


     Objective- Reducing harmonic losses and providing additional harmonic loss handling capacity 

 

  ·  Magnetic design with flux density well below the permissible Bmax for the core material. This provides margin          for additional iron losses   due to harmonics.

  ·  Composite conductor structure design made up of multiple individually insulated parallel conductors of thin               rectangular shape which eliminates the predominant skin effect at higher harmonics resulting in significant               copper loss including eddy current loss and overheating.

  ·   Special coil structure geometries and separated layer of primary and secondory, reduce the magnetic leakage -         stray field-and stray eddy current losses significantly.
 
·  All the above design and structural features reduce the losses due to harmonics significantly.
  ·  However transformers for higher K factor ratings are designed with built-in over sizing to have additional                  thermal  capacity to handle remaining additional losses due to harmonic currents in non - linear  loads.

 ·   Datsons follow the over sizing levels in the design as discussed later. % over sizing may also be provided as per           customeor consultants requirement.

 ·   During heat-run testing of K-rated transformers,the loading is done to the oversized ratings, which simulate the        additional harmonic losses as expected on non-linear loads under real-time application.

  ·  The derating guidelines of UL1561-ANSI 57.110-curves do not apply to transformers with above designs                      considerations and structure.
 

 ·  DOUBLE SIZED NEUTRALS

     Triplen harmonics which form the major part in non linear loads are of zero phase sequence variety and                    therefore get cumulated in the neutral conductor unlike getting cancelled as with fundamental currents causing        excessive heating of neutral conductors and terminals. For K-Factor transformers UL requires that the neutral            terminal and connections are sized to accommodate twice the rated current than phase conductor.


 · SKIN EFFECT AND INCREASED LOSSES AT HIGHER HARMONIC

     With increasing frequency of harmonic currents there is a skin effect of the conductor cross section which results      in the current concentrating on the surface of the conductors, in result reducing the effective cross section of            the conductors. This causes additional heating of the transformer windings as well as the cables and wires                  connecting the system.   



.   MULTI CORE CONDUCTORS

   

    Datsons make k- rated transformer use multi-core conductors for windings which virtually nullify the skin effect         and the resulting increased losses in the windings. It also adapts a rectangular conductor with large aspect ratio        such as 5:1 etc resulting elimination of skin effect further.

·  
LOW FLUX DENSITY MAGNETIC DESIGN


   In order to provide and compensate and provide for core losses due to higher harmonics our K-rated transformers      are designed at 20% lower flux density than conventional transformers. This results in an expensive design.
   
K-rated transformers make use of High grade CRGO low loss high permeability core lamination and are designed at    reduced Bmax – flux density to accommodate additional iron loss due to harmonic currents Electrolytic grade            copper conductors with multiple core cross-sections cancel the eddy losses due to skin effect of higher harmonic         currents.






K-RATED TRANSFORMERS

.

Copyright@2014 Datsons Electronics Pvt.Ltd .

All rights reserved. 

Email:- sales@datsons.com;contact@datsons.com


















































LINEAR LOAS SUCH AS MOTORS,HEATERS, INDUCTORS,CAPACITORS INCANESCENT LIGHTING LOADS ETC


                NON LINEAR LOAD SUCH AS RECTCAP INPUE                   ELECTRONIC LOADS VFD'S, CFL LOGHTING LOAD    COMPUTERS OR SERVER LOAD K-FACTOR                                    

 1   

100%NONEK1

 2

 

100%60-80%K13

 3 


NONE100%K20