K – rated – Isolation Transformers , Cubicles and Distribution Consoles
Any computer Installation with number of Computers and peripherals generate large value of harmonic currents basically for the simple reason that they all have SMPS power supplies at the input. SMPS power supplies have large nonlinear current demands with crest factors in the range of 5 -7.
These harmonic current loads can causes problems in the power system and transformers, such as overheating and premature failure. Conventional Transformers are designed for linear loads and merely de – rating them does not solve the problem.
What are harmonic currents? Harmonic currents are those which have frequencies that are multiples of the fundamental (power supply) 50Hz. The harmonic currents are superimposed on the fundamental current resulting in non- sinusoidal current waveforms associated with nonlinear loads.
What is K- Rating? Underwriters laboratory (UL) has devised a rating system to indicate the capability of a transformer to handle harmonic loads. This is known as it’s K- rating. The ratings are described in UL1561 and are known as transformer
K- factor. K- factor is a weighting of harmonic load currents according to their effects on transformer heating, as derived from ANSI/IEEE C57.110. K-factor of 1.0 indicates a linear load(no harmonics).
The higher the K- factor the greater the harmonic heating effects. K-factor =(l ) xh, Where l is the load current at harmonic – h, expressed per- unit basis, such that the total RMS current equals one. This means that the higher the harmonic number its contribution to K factor is more as it is squared in the formulae.
Design factors in K – rated Transformers
Double Sized Neutral: Triplen harmonics which form the major part in non linear loads are of zero phase sequence variety and hence get cumulated in the neutral conductor, unlike fundamental currents getting cancelled. This Causes excessive heating of neutral conductors and terminals. For K- factor transformers UL requires that the neutral terminal and connections are sized to accommodate twice the rated current than phase conductor.
Multi core conductors: With increasing frequency of harmonic currents there is a skin effect of the conductor cross section which results in the current concentrating on the surface of the conductors. This results in reducing the effective cross section conductors and causes additional heating of the transformer winding and cables connecting the system. Datsons make k- rated transformer use electrolytic grade copper – multi – core conductors for winding which virtually nullifies the skin effect and additional losses in the windings. It also adopts rectangular conductor cross section with large aspect ratio such as 5:1 resulting elimination of the skin effect further.
Low Flux Density magnetic design: In order to compensate and provide for core losses due to higher harmonics currents K – rated transformers are designed at lower flux density than conventional transformers. Essentially all K- rated transformers adopt High permeability low loss CRGO cores and for larger ratings use mitred joint core assemblies.
Built- in Derating: For transformer handling k- rated loads ANSI /IEEE C57.110 recommends method to derate them for different Harmonic load profiles. Transformers directly supplying single – phase power supplies used in all computers and peripherals with SMPS at power input with K factor of 20, require derating of 20-35%
Harmonic Mitigation: K rated transformer design’s primary objective is to handle K rated loads and not to mitigate harmonics But transformers having Delta Star configuration do mitigate triplen harmonic currents in the load currents as they circulate in the Delta primary winding and do not reflect on source side.
| TECHNICAL SPECIFICATIONS of K rated Transformers and other products by DATSONS
|
|||||
| K-rating | K1(Normal) , and K7 , K13 or K20 rating as per requirement with corresponding derating as per UL1561 and ANSI 57.110 guidelines | ||||
| Insulation Class | CLASS H 180 DEG.C designed for higher thermal capacity | ||||
| HV breakdown strength | 2.5 KV AC for 2 Mins | ||||
| Meggar Insulation | > 2 K Megohms | ||||
| Load Regulation and Short Circuit Impedance | load regulation < 3 % and short circuit impedance < 4 % | ||||
| Effeciency | Better than 97 to 98 % depending on capacities @ 100 % load | ||||
| Input Isolator | MCCB of suitable rating and Breakin capacity of 25 KA + according to rating | ||||
| Metering and Indication | See attached table according to Models | ||||
| Cooling | Air Natural / Air Force Suction / Air Force Throw as per table depending on capacities | ||||
| Enclosure | IP31 – Sheet Metal Powder Coated Frame 2.5 MM and Doors 1.6 MM thickness | ||||
| Protections | Short Circuit and Overload Protection by MCCB of suitable Rating | ||||
| Over Temperature alarm and protection by embedded thermostats in winding for higher ratings only. | |||||
| Indicators | Solid State Phase indicators on each phase at input and output | ||||
| Neutral Termination and wiring | Double sized neutral conductor and terminal bus-bar as per UL to handle cumulative Triplen current. | ||||
| Magnetic Design | Designed for lower operatonal flux density to accommodate high harmonic losses using low loss CRGO core lamination | ||||
| Coil design | Designed with reduced current density for handling additional losses due to higher harmonic currents | ||||
| Winding Conductor design | Winding conductor used are multiple core cross section using rectangular strips with large aspect ratio upto 5:1 to eliminate eddy current losses and additional losses due to skin effext. | ||||
| Thermal Rating | Designed for handling non linear loads with higher thermal rating | ||||
| Testing As per IS-2026 | All test facilities as per IS-2026 including Inrush current , heat run temperature rise by res. Measurement | ||||
| Construction | Dry Type Non Encapsulated | ||||

